FlowTest 2.0
SIMULATOR
Bench 1

Set up meters

Enter up to 10 meters of the same type and size, install them in series on the test table and record each as-found reading. Then start a meter test, or run a water-use scenario through them.

1 · Meters

#ManufacturerModelSerial numberLocation / account As-found (gal)Simulated condition
1

Meter 1 is nearest the inlet. The meters are in series, so each one is measured against the same water.

2 · Install on the test table

3 · Test options

• Enter every serial number.
• Install the meters on the test table.
• Record every as-found register reading (0 is fine for a new meter).

Test profile

5/8" Positive displacement
AWWA C700 / M6 · default-2026.1 (verify)

PointFlow gpmVolume galLimits
High 15 10 98.5–101.5%
Intermediate 2 5 98.5–101.5%
Low 0.25 1 95.0–101.5%

Each point runs start/stop: set the flow, stop, tare the weigh tank, read the registers, run the volume, stop, read again.

RESERVOIR VFD · GS20 0.0 Hz STOP 0 A MOTOR PUMP P-1 · 0% V1 0% V2 0% V3 0% 0.000 GPM FT-1 MAG Σ 0.0 gal 0 PT-1 TEST TABLE · OPEN NO METER HYD 0 PT-2 V4 0% DIVERTER → BYPASS WEIGH TANK SCALE · WT-1 0.00 STABLE lb net V5 0%